if you already know who equinex is you know the treat you're in for today for

2
00:00:05,319 --> 00:00:14,080
everyone else equinex who sponsored this facility tour was founded in 1998 and

3
00:00:10,559 --> 00:00:17,199
currently operates over 260 data centers

4
00:00:14,080 --> 00:00:19,359
globally through which flows over half

5
00:00:17,199 --> 00:00:23,519
of the tier one internet backbone in a nutshell if you're using a computer

6
00:00:21,000 --> 00:00:28,439
right now which you probably are like this guy you are more likely than not

7
00:00:25,840 --> 00:00:33,280
touching equinex infrastructure right now and guys I get to take take you deep

8
00:00:30,920 --> 00:00:38,239
behind the curtain I'm talking power data cooling security it's pretty much

9
00:00:35,800 --> 00:00:42,760
everything that we do on our Channel yes even pool server cooling except

10
00:00:50,719 --> 00:00:56,039
legit you see as pretty as it might look

11
00:00:53,960 --> 00:01:00,760
the building behind me was purpose-built from the ground up to be a function

12
00:00:58,680 --> 00:01:05,239
First Data Center and and that manifests in a lot of interesting ways for

13
00:01:02,960 --> 00:01:10,960
starters it was not built from the ground up but rather the first floor was

14
00:01:07,680 --> 00:01:14,960
lifted a few feet off of ground level

15
00:01:10,960 --> 00:01:16,479
why security like any equinex facility

16
00:01:14,960 --> 00:01:20,439
that building needs to be able to withstand a breach attempt from a

17
00:01:18,040 --> 00:01:25,320
vehicle ramming into it but the city wouldn't let them surround it with ugly

18
00:01:22,159 --> 00:01:27,520
barriers so instead they lifted up the

19
00:01:25,320 --> 00:01:34,000
foundation itself so if you drove anything less than that city bus into 45

20
00:01:31,720 --> 00:01:38,560
Parliament Street Toronto you would eventually regain Consciousness and find

21
00:01:36,000 --> 00:01:42,119
the building to be quite unbreached honestly speaking you'd probably have

22
00:01:40,439 --> 00:01:47,240
better luck getting inside if you just walk through the front

23
00:01:43,719 --> 00:01:49,920
door JK once you get in there you'll

24
00:01:47,240 --> 00:01:55,159
find yourself in a series of airlock style doors like this one with at least

25
00:01:52,880 --> 00:02:01,799
three biometric security checkpoints before you so much as catch a glimpse of

26
00:01:57,399 --> 00:02:04,320
a customer rack oo but I get to go but

27
00:02:01,799 --> 00:02:10,000
what's the big deal you might think it's just some servers and network switches

28
00:02:06,399 --> 00:02:12,319
right well yeah but really important

29
00:02:10,000 --> 00:02:16,080
ones equinix houses critical infrastructure for everyone from

30
00:02:14,080 --> 00:02:20,280
telecommunications providers to cloud service providers to Securities

31
00:02:17,720 --> 00:02:24,440
exchanges and even governments to put it in perspective some poor schlub

32
00:02:22,800 --> 00:02:30,000
accidentally overcooked a bag of microwave popcorn at this location and

33
00:02:27,160 --> 00:02:34,480
the city sent seven fir trucks on the off chance that equinex was on fire and

34
00:02:32,560 --> 00:02:38,360
hadn't already Managed IT with their own fire suppression systems for more

35
00:02:36,400 --> 00:02:42,959
context their service level agreement with diesel fuel providers is on par

36
00:02:40,640 --> 00:02:46,400
with the local hospital because well think about it realistically is that

37
00:02:45,000 --> 00:02:53,000
hospital getting anything done without data services probably not let's head up

38
00:02:50,159 --> 00:02:56,840
here's something cool everything in this building except the generators we're

39
00:02:55,080 --> 00:03:01,000
about to see on the fifth floor was brought up in this freight elevator it

40
00:02:59,280 --> 00:03:06,080
has a full ful loaded capacity that's equivalent to about four loaded Mini

41
00:03:03,319 --> 00:03:10,640
Coopers and this is really important for cloud providers who pre-build their

42
00:03:07,799 --> 00:03:15,120
racks offsite it allows them to wheel a rack into their cage hook up power hook

43
00:03:12,959 --> 00:03:20,799
up Cooling and walk away we'll take a look at some of those cages later but

44
00:03:16,799 --> 00:03:23,920
first we need to go all the way up to

45
00:03:20,799 --> 00:03:25,879
the fifth floor where possible equinex

46
00:03:23,920 --> 00:03:29,799
uses a top to bottom approach to building design so we're going to go in

47
00:03:27,720 --> 00:03:34,360
that order why do they design top down you might ask that's because if you

48
00:03:31,480 --> 00:03:38,680
spring a leak it's going to go down so this floor contains everything that's

49
00:03:36,400 --> 00:03:43,640
needed to run the whole building in the event of a major outside Interruption

50
00:03:40,720 --> 00:03:50,000
and nothing can leak on top of it which is especially important for this inside

51
00:03:47,280 --> 00:03:55,400
the apply named battery room is enough capacity to run the entire building at

52
00:03:52,360 --> 00:03:57,920
full load for up to 15 minutes and if

53
00:03:55,400 --> 00:04:02,159
they need more time that's where these come in these diesel generators are

54
00:04:00,120 --> 00:04:10,079
designed to run continuously at a capacity of 2.5 megaw each yes my

55
00:04:05,439 --> 00:04:12,120
friends 2.5 million watts each getting

56
00:04:10,079 --> 00:04:15,599
these up here by the way took some special planning which I'm told involves

57
00:04:14,280 --> 00:04:22,520
cutting a hole in the side of the building renting a crane and then

58
00:04:18,440 --> 00:04:24,880
sliding them in absolutely badass but

59
00:04:22,520 --> 00:04:29,880
there's one small problem now they've got to fuel them I mean they've got this

60
00:04:27,560 --> 00:04:35,800
little Reservoir here but this one run one of these bad boys for what an

61
00:04:32,639 --> 00:04:38,360
hour well as it turns out the main tanks

62
00:04:35,800 --> 00:04:43,320
which include an onsite polisher to remove water and other impurities that

63
00:04:40,360 --> 00:04:47,880
can spoil the fuel those are underground and this was done because diesel fuel is

64
00:04:45,360 --> 00:04:53,199
lighter than water and equinex wanted to design this building such that if the

65
00:04:50,320 --> 00:04:57,880
entire first floor was flooded the tanks wouldn't float away Wicked smart the

66
00:04:56,320 --> 00:05:04,840
last thing they had to manage was the noise oh the noise noise noise

67
00:05:01,400 --> 00:05:07,160
noise now obviously equinex isn't going

68
00:05:04,840 --> 00:05:11,919
to hit their 2030 renewable energy goals by running diesel generators 247 but

69
00:05:10,199 --> 00:05:15,199
they do need to perform monthly checks on them and I'm told that when you fire

70
00:05:13,600 --> 00:05:19,919
those things up you can't even hear yourself think in here now given there

71
00:05:17,759 --> 00:05:26,039
used to be a public library on the other side of this wall that was a problem so

72
00:05:23,319 --> 00:05:30,240
equinix designed These acoustic baffles that Bring the Noise down to the same as

73
00:05:27,919 --> 00:05:34,400
a typical City Road and you can oh wow can you can probably

74
00:05:32,720 --> 00:05:40,160
hear the difference right when I go in there oh yeah crazy kind of necessary if

75
00:05:38,039 --> 00:05:46,080
you consider that this is about the equivalent of having five bloody trains

76
00:05:42,880 --> 00:05:48,120
running in here fun fact before we leave

77
00:05:46,080 --> 00:05:52,000
this room by the way diesel generation kicks off enough smoke that conventional

78
00:05:50,360 --> 00:05:57,840
smoke detectors would be giving off constant false alarms so this room uses

79
00:05:54,880 --> 00:06:02,919
flame detectors special cameras that can see through smoke to see if there's

80
00:06:00,080 --> 00:06:08,440
actual fire moving into the chiller room we've got the exact opposite problem you

81
00:06:05,319 --> 00:06:11,199
can fit so much water in this bad boy

82
00:06:08,440 --> 00:06:16,440
that is why absolutely no customer infrastructure is allowed under this

83
00:06:13,560 --> 00:06:20,800
room in here are three main cooling Loops the one behind me is filled with

84
00:06:18,639 --> 00:06:25,840
antifreeze that goes between these liquid to liquid Heat exchangers and the

85
00:06:23,280 --> 00:06:29,160
large evaporative cooling fin Stacks that are Up on the Roof we're going to

86
00:06:27,520 --> 00:06:34,160
take a closer look at those in a minute but for now now I want to look at the

87
00:06:31,520 --> 00:06:39,639
other Loops those two are connected to what is in effect the biggest freaking

88
00:06:37,400 --> 00:06:45,240
air conditioner that I have ever seen except instead of cooling air like your

89
00:06:42,039 --> 00:06:47,919
air conditioner does it cools water the

90
00:06:45,240 --> 00:06:52,319
hot side here carries heat to those same heat exchangers that we just talked

91
00:06:49,759 --> 00:06:56,919
about while the cold side is connected to the rest of the building through what

92
00:06:54,080 --> 00:07:01,520
equinex calls their bus architecture which is kind of just a fancy way of

93
00:06:59,039 --> 00:07:06,520
saying that it's all redundant it's all interconnected and it's all controlled

94
00:07:03,720 --> 00:07:10,520
by a BMS or building management system and I'll show you why that's cool right

95
00:07:08,440 --> 00:07:15,440
above me is our chilled water return which is bringing heat up from the data

96
00:07:12,520 --> 00:07:22,199
center floors below okay so far so simple but where does it go

97
00:07:19,039 --> 00:07:25,240
well as you can see it gets a little

98
00:07:22,199 --> 00:07:27,879
complicated when it's below 4° C in

99
00:07:25,240 --> 00:07:31,479
Canadian winter it essentially passes straight through with the compressors

100
00:07:29,639 --> 00:07:36,599
barely running and goes to the heat exchangers on the roof sweet free

101
00:07:33,879 --> 00:07:41,199
cooling thanks Mother Nature but then spring rolls around and the outside air

102
00:07:39,120 --> 00:07:45,039
needs some help that's when our highly efficient magnetic bearing compressors

103
00:07:43,240 --> 00:07:50,759
ramp up their cooling efforts bringing our thermals under control but wait now

104
00:07:48,120 --> 00:07:57,000
it's Midsummer and there's a heat Dome we need more cooling Captain thankfully

105
00:07:54,159 --> 00:08:02,440
we've got it now most of the time the misters are not needed but for a

106
00:07:59,960 --> 00:08:08,039
building like this you don't design for most of the time and these rooftop fin

107
00:08:04,840 --> 00:08:10,280
Stacks can either be run bare or they

108
00:08:08,039 --> 00:08:14,440
can be lightly coated in water to dramatically increase their cooling

109
00:08:12,039 --> 00:08:20,560
capacity it works in the same way that your arm gets much colder if you lick it

110
00:08:17,759 --> 00:08:25,759
before you blow on it the best part is that everything we've seen is fully

111
00:08:23,080 --> 00:08:30,199
redundant including cold spares of key components that gives equinix's team

112
00:08:28,240 --> 00:08:33,760
lots of options for load balancing during maintenance and it means that in

113
00:08:32,159 --> 00:08:39,919
the event of an equipment failure or another event equinex won't risk giving

114
00:08:36,240 --> 00:08:42,479
up their nice 69 uptime Target that's an

115
00:08:39,919 --> 00:08:48,320
average of about 32 seconds of downtime per year by the way wow hilariously

116
00:08:46,320 --> 00:08:51,839
sometime in the near future all the cooling we just looked at will be

117
00:08:49,600 --> 00:08:57,000
rendered redundant though when the forth pipe goes online in the dlwc or deep

118
00:08:54,839 --> 00:09:01,480
lake water cooling system if you haven't heard of it it's basically my pool water

119
00:08:59,200 --> 00:09:06,800
cool cooling setup except done properly with massive pipes that draw 4° water

120
00:09:04,680 --> 00:09:12,240
from the bottom of Lake Ontario and then pump it into the city to cool office

121
00:09:08,720 --> 00:09:14,760
towers and Arenas and well data centers

122
00:09:12,240 --> 00:09:19,720
that sort of thing super cool project since we're up here by the way these

123
00:09:16,760 --> 00:09:23,839
freaking blew my mind now as consumers when we want the lowest latency say for

124
00:09:21,800 --> 00:09:30,079
gaming or video conferencing we think fiber right well what if I told you that

125
00:09:26,760 --> 00:09:33,519
there's a tier above the speed of light

126
00:09:30,079 --> 00:09:35,880
well you'd probably tell me there is not

127
00:09:33,519 --> 00:09:41,440
and all right you got me but here's the thing light does not always go the same

128
00:09:39,040 --> 00:09:46,519
speed and fiber optic cable slows it down to about 2/3 of its theoretical

129
00:09:44,480 --> 00:09:51,120
maximum in a vacuum now that's not enough to matter for your game but for

130
00:09:48,720 --> 00:09:55,040
Capital Market transactions where micros seconds can be the difference between

131
00:09:52,800 --> 00:09:59,959
making your trade and losing a huge opportunity every Competitive Edge

132
00:09:57,480 --> 00:10:05,560
matters and that is where these microwave arrays come in these provide

133
00:10:03,200 --> 00:10:10,560
direct line of sight links North to the Toronto Stock Exchange and South to New

134
00:10:08,160 --> 00:10:15,440
York now of course for anything where throughput matters nobody's using these

135
00:10:13,440 --> 00:10:19,480
so let's go back inside and look at good oldfashioned fiber by the way you guys

136
00:10:17,720 --> 00:10:22,839
might have noticed some extra pads and footings for additional equipment up

137
00:10:21,120 --> 00:10:26,399
here that's another nice thing about a purpose-built building you can plan out

138
00:10:24,800 --> 00:10:30,920
your future capacity and then you can build it as needed this for instance is

139
00:10:28,720 --> 00:10:35,560
a spot for another fin stack and here in the electrical room you'll see much of

140
00:10:32,839 --> 00:10:39,680
the same thing look at the Glorious extra conduit for future installs isn't

141
00:10:38,880 --> 00:10:45,600
it beautiful this room takes in

142
00:10:42,480 --> 00:10:48,040
13,800 volt power steps it down and

143
00:10:45,600 --> 00:10:51,800
distributes it throughout the building but all right enough about

144
00:10:49,880 --> 00:10:57,360
infrastructure how about some customer systems right the next two floors are

145
00:10:54,440 --> 00:11:01,880
very similar so let's go with number four this is the oldest floor and

146
00:10:59,920 --> 00:11:06,480
therefore uses some older design paradigms for starters cooling is

147
00:11:04,240 --> 00:11:10,160
handled using cold Isle containment rather than hot aisle containment and

148
00:11:08,160 --> 00:11:15,040
let me show you what that means the water from above us is getting pumped

149
00:11:12,720 --> 00:11:19,720
into this air handler Corridor that chills the air chilled air then gets

150
00:11:17,480 --> 00:11:27,560
carried through ducts to the center of the customer's cage where a thermal

151
00:11:23,200 --> 00:11:30,200
probe aha will inform the system when

152
00:11:27,560 --> 00:11:36,320
cooling is needed it opens up the motorized Vents and then blasts cold air

153
00:11:33,519 --> 00:11:40,480
downward it then gets sucked up into the rack which is going to be on either side

154
00:11:38,480 --> 00:11:45,600
and then exhausted out into the room where it gets sucked into that Corridor

155
00:11:42,760 --> 00:11:50,720
rinse and repeat now the main drawback of this approach is that it allows some

156
00:11:48,120 --> 00:11:55,560
mixing of the hot and cold air but equinex still managed a solid power

157
00:11:53,480 --> 00:12:00,360
usage effectiveness of 1.42 for this site since you're

158
00:11:58,240 --> 00:12:05,320
wondering by the way I should probably acknowledge that this is an Unleashed

159
00:12:03,160 --> 00:12:10,399
space and there are normally strict rules about access to these cages for

160
00:12:07,920 --> 00:12:16,680
example exchanges cannot have their cages entered at all during trading

161
00:12:13,199 --> 00:12:19,079
hours and even for equinex staff unless

162
00:12:16,680 --> 00:12:23,680
there's an emergency or contracted work that needs to be done they are not

163
00:12:21,560 --> 00:12:28,600
supposed to be entering customer spaces so they built these cool access panels

164
00:12:26,519 --> 00:12:33,480
where they can run any connections that the customer requests to the outside of

165
00:12:31,079 --> 00:12:38,320
the cage and then the customer can come in and Route whatever they need for

166
00:12:35,920 --> 00:12:42,920
whatever they're doing access to the cages is controlled by access cards and

167
00:12:40,680 --> 00:12:48,959
Biometrics either a hand or a fingerprint that's stored as a hash for

168
00:12:45,399 --> 00:12:51,880
customer privacy and any use of your

169
00:12:48,959 --> 00:12:56,600
card is logged on top of the logs for the biometric sensor the contact sensor

170
00:12:54,279 --> 00:13:01,279
on the door the motion sensor near the door ah there it is and of course the

171
00:12:59,560 --> 00:13:07,199
camera pointed at the back of the rack space and if all this seems Overkill You

172
00:13:04,240 --> 00:13:12,440
Ain't Seen Nothing Yet many of the cages not only have physical access barriers

173
00:13:09,959 --> 00:13:18,160
but even visual blockers so no one can see any of the equipment in use and for

174
00:13:15,480 --> 00:13:22,600
the extra paranoid a top cage can be installed to ensure that nobody can

175
00:13:20,040 --> 00:13:26,040
climb over the top though of course anyone trying to do that would have been

176
00:13:24,000 --> 00:13:30,440
spotted by one of the hundreds of cameras in this place but then as you

177
00:13:28,760 --> 00:13:36,000
probably picked up by now in this business redundancy is the name of the

178
00:13:32,959 --> 00:13:38,600
game some cages go even further

179
00:13:36,000 --> 00:13:43,880
requiring what's called double access meaning that to get inside you need both

180
00:13:41,160 --> 00:13:49,160
an equinex employee and a customer employee and we even saw one with a

181
00:13:46,560 --> 00:13:53,759
touch sensitive cage so if you so much as leaned against it a ticket would get

182
00:13:51,600 --> 00:13:58,720
automatically created and equinex security would get an Irate phone call

183
00:13:55,880 --> 00:14:04,199
but wait there's more they told me that some customers will even post a guard

184
00:14:01,519 --> 00:14:09,240
who stands outside their cage 24 hours a day 7 days a week financial institutions

185
00:14:07,399 --> 00:14:14,120
and government agencies will often operate with a high degree of security

186
00:14:11,160 --> 00:14:18,959
like that speaking of financial institutions certain customers have

187
00:14:16,880 --> 00:14:24,279
noticed that if they're closer to each other they can have a physical advantage

188
00:14:21,240 --> 00:14:26,880
in connection times well that's not

189
00:14:24,279 --> 00:14:32,360
necessarily a good thing to solve that problem then equinex has a system called

190
00:14:29,399 --> 00:14:37,560
equidistant trading that neutralizes any latency Advantage by running the exact

191
00:14:34,880 --> 00:14:42,600
same length of fiber to every customer who requires that the spools of excess

192
00:14:40,399 --> 00:14:47,680
fiber optic cable are one of the most protected things in the entire facility

193
00:14:45,519 --> 00:14:52,560
now I was able to convince them to open the door earlier for a quick b-roll shot

194
00:14:50,199 --> 00:14:56,959
but they wouldn't let us any closer there's a camera pointed at the cabinet

195
00:14:54,720 --> 00:15:02,120
and if anyone so much as goes near it security shows up and it's a whole to do

196
00:14:59,600 --> 00:15:07,800
with reports to the SEC and the whole kazoo moving on to the second floor this

197
00:15:04,959 --> 00:15:11,880
place is sick now we weren't able to shoot as much here due to customer

198
00:15:09,519 --> 00:15:16,360
privacy concerns but we did manage to get some footage of one of the liquid

199
00:15:13,560 --> 00:15:20,759
cooled cages here building cold water goes into a heat exchanger that pumps

200
00:15:18,800 --> 00:15:25,880
chilled water to their highdensity servers these kinds of deployments are

201
00:15:23,079 --> 00:15:30,959
becoming much more common but they're kind of an ongoing challenge for

202
00:15:27,800 --> 00:15:33,680
standards lovers equinex at the moment

203
00:15:30,959 --> 00:15:38,959
these guys dial in flipping everything down to the colors of the metal posts in

204
00:15:36,199 --> 00:15:45,880
their facilities by the way blue means you hang stuff off them and gray means

205
00:15:41,720 --> 00:15:47,639
they hold stuff up the more you know but

206
00:15:45,880 --> 00:15:52,680
the lack of standards in the liquid cooling space right now means that these

207
00:15:49,959 --> 00:15:56,079
cages often need special provisions and that's something that they're working

208
00:15:53,800 --> 00:16:02,120
with others in the industry to solve as rack power density continues to scale to

209
00:15:58,680 --> 00:16:03,360
l ludicrous levels looking at you AI

210
00:16:02,120 --> 00:16:07,759
while we're here there's a couple other cool things about this cage there's leak

211
00:16:05,639 --> 00:16:11,920
containment troughs in the ceiling under any water pipes to ensure that even a

212
00:16:09,759 --> 00:16:16,319
small leak will be caught and can't fall onto the equipment below it and if you

213
00:16:14,319 --> 00:16:20,720
look carefully at the floor there's actually little yellow ropes running

214
00:16:18,399 --> 00:16:24,920
around the outside of this cage and here on the first floor I see another one now

215
00:16:23,360 --> 00:16:29,160
I wouldn't blame you guys for thinking gee it seems uncharacteristically sloppy

216
00:16:27,600 --> 00:16:34,920
of these guys to leave this kind of thing lying around all over the place

217
00:16:31,680 --> 00:16:36,600
but it's actually not a rope they are

218
00:16:34,920 --> 00:16:40,839
everywhere in this facility where there's water and they're part of a leak

219
00:16:38,680 --> 00:16:48,079
detection system that tells their team not only if there's been a leak but

220
00:16:43,639 --> 00:16:49,759
exactly exactly where it was boy would

221
00:16:48,079 --> 00:16:54,480
that ever have been handy boy would that ever have been handy boy would that ever

222
00:16:51,519 --> 00:16:58,440
been handy since we're here by the way this happens to be the newest floor in

223
00:16:56,240 --> 00:17:02,399
the building remember top to bottom buildout right this one was done about a

224
00:17:00,680 --> 00:17:07,880
year ago and they refer to this data Hall as a as a mark1 design but now that

225
00:17:05,919 --> 00:17:12,079
AI has exploded power densities to numbers that would have been Unthinkable

226
00:17:09,360 --> 00:17:17,160
even 2 to 3 years ago the mark 2 designs that they're currently constructing are

227
00:17:13,720 --> 00:17:19,559
aiming at around 10 times the power per

228
00:17:17,160 --> 00:17:25,319
square foot that they targeted here so maybe that's something we could see in

229
00:17:20,919 --> 00:17:27,079
another video equinex andho this floor

230
00:17:25,319 --> 00:17:32,520
uses a very different system for handling Air instead of pushing cold air

231
00:17:29,480 --> 00:17:35,400
to the cages now they pull hot air out

232
00:17:32,520 --> 00:17:40,480
of the cages into these chimneys that go up into the plenum which runs into the

233
00:17:37,480 --> 00:17:42,880
air handlers now it might seem like an

234
00:17:40,480 --> 00:17:46,640
unimportant distinction but the higher the temperature difference the more

235
00:17:44,760 --> 00:17:51,919
efficient the thermal transfer and when you're dealing with very high draw racks

236
00:17:49,720 --> 00:17:57,480
this ensures that the hottest possible air goes into the handling it also all

237
00:17:55,000 --> 00:18:02,360
but completely prevents hot and cold air from mixing which is a major winre

238
00:17:59,640 --> 00:18:07,880
efficiency now I can practically hear you guys shouting if you've got all the

239
00:18:04,880 --> 00:18:10,159
hot air in a chimney why don't you do

240
00:18:07,880 --> 00:18:15,120
what a chimney does best and blast it out of the building well you can do that

241
00:18:13,080 --> 00:18:19,880
but then you need to bring in air to replace it air that needs to be filtered

242
00:18:17,440 --> 00:18:26,200
and that needs to be humidity controlled to handle that at the kind of volume

243
00:18:22,280 --> 00:18:28,440
that you would need it's impractical so

244
00:18:26,200 --> 00:18:33,400
even under very extreme conditions like we saw last winter in Chicago I'm sorry

245
00:18:31,000 --> 00:18:37,679
but you can't just swing open the doors of a Data Center and hope that it'll run

246
00:18:35,559 --> 00:18:41,799
cooler by the way we didn't show this on the other customer floors but there's

247
00:18:39,480 --> 00:18:47,159
actually two equivalent air handling systems on opposite sides of each floor

248
00:18:45,280 --> 00:18:51,679
each with the capacity to handle the entire floor in the event of a failure

249
00:18:50,120 --> 00:18:57,080
by the way before we leave the customer systems area I was very surprised to

250
00:18:54,360 --> 00:19:02,159
hear that equinex does not use exotic fire suppression methods op instead for

251
00:18:59,559 --> 00:19:07,799
standard water sprinklers but then I found out they're not quite standard see

252
00:19:05,240 --> 00:19:12,720
the pipes are not flooded with water all the time but rather they're full of

253
00:19:09,480 --> 00:19:16,000
inert gas and water only flows into them

254
00:19:12,720 --> 00:19:18,280
if two out of three systems go off and a

255
00:19:16,000 --> 00:19:24,679
plastic head melt so they use heat detection smoke detection and the

256
00:19:21,080 --> 00:19:27,600
world's most expensive PVC runs these

257
00:19:24,679 --> 00:19:32,280
are part of a vesda or very early smoke detection alarm system system that can

258
00:19:29,640 --> 00:19:37,080
not only detect smoke but also triangulate where it's coming from to

259
00:19:34,720 --> 00:19:41,159
ensure that only the necessary sprinkler head goes off they made this choice

260
00:19:39,520 --> 00:19:45,360
because oxygen depletion fire suppression can pose very real risks to

261
00:19:43,880 --> 00:19:51,559
any Personnel who get accidentally trapped so good guy equinex let's go to

262
00:19:49,000 --> 00:19:55,840
the basement above me is where utility power comes into the building or rather

263
00:19:53,600 --> 00:20:01,679
this is one of the two rooms because redundancy right now interestingly the

264
00:19:59,159 --> 00:20:06,200
power company can actually control this unit remotely allowing them to turn it

265
00:20:03,880 --> 00:20:13,520
on and off and even scale how much power comes in that is not a normal thing but

266
00:20:10,400 --> 00:20:16,159
because there's so much power going into

267
00:20:13,520 --> 00:20:22,159
this building in an emergency they might need to call equinix and say hey um we

268
00:20:19,679 --> 00:20:26,159
need more power could you guys just turn all of this off and Island yourselves

269
00:20:24,240 --> 00:20:30,120
this kind of collaboration is really important because equinex estimates that

270
00:20:28,520 --> 00:20:35,919
this this building draws somewhere in the neighborhood of 3% of the city's

271
00:20:32,559 --> 00:20:38,240
entire power budget if a multi megawatt

272
00:20:35,919 --> 00:20:42,840
load kicks in suddenly without warning or drops suddenly without warning it is

273
00:20:40,320 --> 00:20:47,480
a big problem for grid stability with that said they do turn it off and on

274
00:20:45,200 --> 00:20:52,200
regularly though every year they do a scheduled pull the plug test and

275
00:20:49,919 --> 00:20:56,400
quarterly they do load tests where they will bring in load Banks to ensure that

276
00:20:54,679 --> 00:20:59,840
the building can actually power everything that it's rated for these

277
00:20:58,120 --> 00:21:03,799
things sound pretty cool basically if they don't have enough servers running

278
00:21:01,320 --> 00:21:09,480
they bring in Big Blocks of metal and they fire up the generators and make

279
00:21:05,320 --> 00:21:11,600
them glow red hot flipping wild finally

280
00:21:09,480 --> 00:21:15,000
there's the fiber in room it's funny they thought that this was going to be

281
00:21:13,120 --> 00:21:19,080
underwhelming and they were all like are you sure you even want to see it but it

282
00:21:17,159 --> 00:21:23,640
really goes to show you how numb you can get to cool stuff if you spend your

283
00:21:20,880 --> 00:21:28,200
whole day around it now in fairness to them they are kind of right I mean it

284
00:21:26,520 --> 00:21:34,039
pretty much looks exactly like the fiber room our building back home line comes

285
00:21:30,559 --> 00:21:36,320
in from outside line loops around as is

286
00:21:34,039 --> 00:21:42,080
tradition and then gets spliced or patched to wherever the difference is

287
00:21:39,960 --> 00:21:47,640
that I could probably fit my entire family hula hooping inside these

288
00:21:44,799 --> 00:21:53,080
freaking loops and where they go to is even cooler they go outside to one of

289
00:21:51,080 --> 00:21:58,760
the seven manholes that get shared by the approximately 60 carriers that route

290
00:21:55,960 --> 00:22:05,200
into this building that is what the carrier's access ends equinix splices

291
00:22:02,600 --> 00:22:10,039
runs from the manholes to this room and then they run it up to the floors above

292
00:22:07,880 --> 00:22:15,400
the carriers only get access again once it reaches their cage this is how

293
00:22:13,000 --> 00:22:20,880
equinex enforces the principle of equity of access that inspired their name oh

294
00:22:18,880 --> 00:22:25,080
and of course there are two of these rooms with fiber coming in from two

295
00:22:23,120 --> 00:22:28,880
different sides of the building because in the event of a construction worker

296
00:22:26,880 --> 00:22:33,400
accidentally cutting one of these or something they got to have redundancy I

297
00:22:31,240 --> 00:22:37,320
got to tell you guys there is so much we weren't able to fully cover if you

298
00:22:35,000 --> 00:22:41,559
noticed QR codes on everything those are cool they use AR to direct technicians

299
00:22:39,799 --> 00:22:46,120
for fault Discovery and to map out customer connection requests um the

300
00:22:43,640 --> 00:22:50,159
18-wheeler dock can be completely closed off for privacy and security when you're

301
00:22:48,080 --> 00:22:54,760
unloading racks uh they have employee facilities on site so when an emergency

302
00:22:52,520 --> 00:22:58,799
you can shower shave sleep you know your 3 s's um they turn off the lights

303
00:22:56,960 --> 00:23:02,600
whenever no humans are detected to save power they've got grounding strips

304
00:23:00,640 --> 00:23:06,720
freaking everywhere they have direct links to their other buildings to turn

305
00:23:04,480 --> 00:23:12,039
their entire flock of data centers into a giant redundant mesh guys there is so

306
00:23:10,000 --> 00:23:16,400
much more but I think it might have to wait for next time for now massive

307
00:23:14,840 --> 00:23:20,760
thanks to equinix for sponsoring this video and giving us such an in-depth

308
00:23:18,640 --> 00:23:25,320
look at the kind of space that most people are never going to set foot in

309
00:23:22,520 --> 00:23:28,600
let alone get a comprehensive tour of hopefully we'll get a chance to do it

310
00:23:26,679 --> 00:23:32,760
again sometime if you guys enjoyed this video hey you might enjoy this kind of

311
00:23:30,760 --> 00:23:38,679
high security nobody gets to see it kind of stuff so maybe check out the Intel

312
00:23:34,840 --> 00:23:38,679
Fab tour that we did last year